lamaPLC: Communication with Eastron Smart X96
The Smart X96-5 is a high accuracy multifunction power meter that is a traditional wired 1/5A current transformer operated meter. Configurable for 1p2w, 3p3w and 3p4w systems and hosting a vast range of measuring parameters such as Amps, Volts, Power, Power and Current Demand (Sliding and fix scale options), Power Factor, imported and exported kWh, Individual harmonics, Phase sequence and a phase summary page. It is one of the most user-friendly multifunction power meters in the market form installation to end client use.
It is typical in most installations that the current transformers are mounted on the left-hand side of the breaker so P1 is facing the correct way. However, it is also possible to mount the current transformer on the right-hand side with P2 facing the breaker. This is possible due to the meter having the option to reverse the flow to correct this type of application.
The SMART X96-5 requires mains voltage inputs and external current transformers in order to operate, it is self-supplied via a internal three phase transformer, this means if any of the phases fail the meter will remain powered and does not require an external auxiliary supply. The Smart X96-5 meter comes complete with RS485 Modbus RTU and dual pulsed outputs as standard.
- MID Certified to Class C (0.5%) accuracy
- Designed and tested in the UK by an independent laboratory
- 1/5A Current transformer operated
- Individual harmonics up to 63rd level (Class 1)
- Internal three phase power supply
- Highly visible backlit display from all angles
- Programmable reverse flow for right/left side of breaker CT installation.
- Built in Modbus and Pulsed outputs
Modbus map
input register | Measurement | Variable | Unit | Note |
---|---|---|---|---|
30000 | Phase 1 line to neutral volts | Float | V | 1: Basis 0, 0x00, 79 words |
30002 | Phase 2 line to neutral volts | Float | V | 0x02 |
30004 | Phase 3 line to neutral volts | Float | V | 0x04 |
30006 | Phase 1 current | Float | A | 0x06 |
30008 | Phase 2 current | Float | A | 0x08 |
30010 | Phase 3 current | Float | A | 0x0A |
30012 | Phase 1 active power | Float | W | 0x0C |
30014 | Phase 2 active power | Float | W | 0x0E |
30016 | Phase 3 active power | Float | W | 0x10 |
30018 | Phase 1 apparent power | Float | VA | 0x12 |
30020 | Phase 2 apparent power | Float | VA | 0x14 |
30022 | Phase 3 apparent power | Float | VA | 0x16 |
30024 | Phase 1 reactive power | Float | VAr | 0x18 |
30026 | Phase 2 reactive power | Float | VAr | 0x1A |
30028 | Phase 3 reactive power | Float | VAr | 0x1C |
30030 | Phase 1 power factor | Float | None | 0x1E Positive: forward current, negative: reverse current |
30032 | Phase 2 power factor | Float | None | 0x20 Positive: forward current, negative: reverse current |
30034 | Phase 3 power factor | Float | None | 0x22 Positive: forward current, negative: reverse current |
30036 | Phase 1 phase angle | Float | ° | 0x24 |
30038 | Phase 2 phase angle | Float | ° | 0x26 |
30040 | Phase 3 phase angle | Float | ° | 0x28 |
30042 | Average line to neutral volts | Float | V | 0x2A |
30046 | Average line current | Float | A | 0x2E |
30048 | Sum of line currents | Float | A | 0x30 |
30052 | Total system power | Float | W | 0x34 |
30056 | Total system volt amps | Float | VA | 0x38 |
30060 | Total system V Ar | Float | VAr | 0x3C |
30062 | Total system power factor | Float | None | 0x3E Positive: forward current, negative: reverse current |
30066 | Total system phase angle | Float | Degrees | 0x42 |
30070 | Frequency of supply voltages | Float | Hz | 0x46 |
30072 | Import Wh since last reset | Float | kWh | 0x48 |
30074 | Export Wh since last reset | Float | kWh | 0x4A |
30076 | Import V Arh since last reset | Float | kVArh | 0x4C |
30078 | Export V Arh since last reset | Float | kVArh | 0x4E |
30080 | VAh since last reset | Float | kVAh | 2: Basis 0x50 (80), 31 words |
30082 | Ah since last reset | Float | Ah | 0x52 |
30084 | Total system power demand | Float | W | 0x54 The power sum demand calculation is for import - export |
30086 | Maximum total system power demand | Float | W | 0x56 The power sum demand calculation is for import - export |
30088 | Import active power demand | Float | W | 0x58 |
30090 | Import active power max. demand | Float | W | 0x5A |
30092 | Export active power demand | Float | W | 0x5C |
30094 | Export active power max. demand | Float | W | 0x5E |
30100 | Total system VA demand | Float | VA | 0x64 |
30102 | Maximum total system VA demand | Float | VA | |
30104 | Neutral current demand | Float | A | |
30106 | Maximum neutral current demand | Float | A | |
30108 | Total system reactive power demand | Float | VAr | The power sum demand calculation is for import - export |
30110 | Maximum total system reactive power demand | Float | VAr | |
30160 | Voltage phase sequence (normal= 1, reverse=2) | Float | None | |
30162 | Current phase sequence (normal= 1, reverse=2) | Float | None | |
30192 | Nature of the load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30194 | Nature of L1 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30196 | Nature of L2 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30198 | Nature of L3 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30200 | Line 1 to Line 2 volts | Float | V | |
30202 | Line 2 to Line 3 volts | Float | V | |
30204 | Line 3 to Line 1 volts | Float | V | |
30206 | Average line to line volts | Float | V | |
30224 | Neutral current | Float | A | |
30234 | Phase 1 LIN volts THD | Float | % | |
30236 | Phase 2 LIN volts THD | Float | % | |
30238 | Phase 3 LIN volts THD | Float | % | |
30240 | Phase 1 Current THD | Float | % | |
30242 | Phase 2 Current THD | Float | % | |
30244 | Phase 3 Current THD | Float | % | |
30248 | Average line to neutral volts THD | Float | % | |
30250 | Average line current THD | Float | % | |
30258 | Phase 1 current demand | Float | A | |
30260 | Phase 2 current demand | Float | A | |
30262 | Phase 3 current demand | Float | A | |
30264 | Maximum phase 1 current demand | Float | A | |
30266 | Maximum phase 2 current demand | Float | A | |
30268 | Maximum phase 3 current demand | Float | A | |
30334 | Line 1 to line 2 volts THD | Float | % | |
30336 | Line 2 to line 3 volts THD | Float | % | |
30338 | Line 3 to line 1 volts THD | Float | % | |
30340 | Average line to line volts THD | Float | % | |
30342 | Total kwh | Float | kWh | Total kWh/ kVarh equals to Import+ export |
30344 | Total kvarh | Float | kVArh | Total kWh/ kVarh equals to Import+ export |
30346 | LI import kwh | Float | kWh | |
30348 | L2 import kwh | Float | kWh | |
30350 | L3 import kWh | Float | kWh | |
30352 | LI export kWh | Float | kWh | |
30354 | L2 export kwh | Float | kWh | |
30356 | L3 export kWh | Float | kWh | |
30358 | LI total kwh | Float | kWh | |
30360 | L2 total kWh | Float | kWh | |
30362 | L3 total kwh | Float | kWh | |
30364 | LI import kvarh | Float | kVArh | |
30366 | L2 import kvarh | Float | kVArh | |
30368 | L3 import kvarh | Float | kVArh | |
30370 | LI export kvarh | Float | kVArh | |
30372 | L2 export kvarh | Float | kVArh | |
30374 | L3 export kvarh | Float | kVArh | |
30376 | LI total kvarh | Float | kVArh | |
30378 | L2 total kvarh | Float | kVArh | |
30380 | L3 total kvarh | Float | kVArh | |
30402 | Voltage 2st- 63st Harmonic L1 | 62*Float | % | |
30526 | Voltage 2st- 63st Harmonic L2 | 62*Float | % | |
30650 | Voltage 2st- 63st Harmonic L3 | 62*Float | % | |
30774 | Current 2st- 63st Harmonic L1 | 62*Float | % | |
30898 | Current 2st- 63st Harmonic L2 | 62*Float | % | |
31022 | Current 2st- 63st Harmonic L3 | 62*Float | % | |
31146 | Voltage Total Harmonic L1 | Float | % | |
31148 | Voltage Total Harmonic L2 | Float | % | |
31150 | Voltage Total Harmonic L3 | Float | % | |
31152 | Current Total Harmonic L1 | Float | % | |
31154 | Current Total Harmonic L2 | Float | % | |
31156 | Current Total Harmonic L3 | Float | % |