meta data for this page
  •  

This is an old revision of the document!


LamaPLC: Eastron SDM 230 Communication

Eastron SDM230

The Eastron SDM230-Modbus MID 1-phase kWh meter is ideal for the precise monitoring of, for example, a solar panel system, a charging station, a heat pump or another 1-phase group of your choice. On the illuminated LCD screen, you can immediately see how many kWh the respective system consumes or produces and is used for official registration and billing of the measurement data. For example, if you want to bill a tenant for the electricity consumption of a specific room.

RS485 communication interface, MODBUS RTU protocol:

  • Baudrate: 9600 Baud (default, can set)
  • Parity: Even
  • Databits: 8
  • Stopbits: 1
  • Default slave ID: 45
  • Number of Drivers and Receivers: 32 Drivers, 32 Receivers (without repeater)
  • Maximum Cable Length: 1200 m
  • Maximum Data Rate: 10 Mbaud
  • Maximum Common Mode Voltage: 12 V .. –7 V
  • Minimum Driver Output Levels (Loaded): +/– 1.5 V
  • Minimum Driver Output Levels (Unloaded): +/– 6 V
  • Drive Load: Minimum 60 ohms
  • Driver Output Short Circuit Current Limit: 150 mA to Gnd, 250 mA to 12 V, 250 mA to -7 V
  • Minimum Receiver Input Resistance: 12 kΩ
  • Receiver Sensitivity: +/- 200 mV

32 bit (2 words) input registers

The registers are read-only.

CodeRegister NrDescriptionTypeUnitModbus
blocks
1st modbus block
V130000Line neutral voltFloatVBasis 0x00, words: 37
C130006CurrentFloatA0x06
ACP130012Active powerFloatW0x0C
APP130018Apparent powerFloatVA0x12
RAP130024Reactive powerFloatVAr0x18
PF130030Power factorFloat-0x1E
PA130036Phase angleFloat°0x24
FR130070FrequencyFloatHzBasis 0x00, words: 37
IACE130072Import active energyFloatkWh
EACE130074Export active energyFloatkWh
IRAE130076Import reactive energyFloatkvarh
ERAE130078Export reactive energyFloatkvarh
TP30084Total system power demandFloatW
-30086Maximum total system power demandFloatW
-30088Current system positive power demandFloatW
-30090Maximum system positive power demandFloatW
-30092Current system reverse power demandFloatW
-30094Maximum system reverse power demandFloatW
-30258Current demandFloatA
-30264Maximum current demandFloatA
TAE30342Total active energyFloatkWh
TRE30344Total reactive energyFloatkvarh
-30384Current resettable total active energyFloatkWh
-30386Current resettable total reactive energyFloatkvarh
MA40020Modbus node address
RW, default 45
Float-
MBR40028Modbus baud rate
RW, 0 = 2400 bps(default) 1 = 4800 bps 2 = 9600 bps 5=1200 bps
Float-