The Smart X96-5 is a high accuracy multifunction power meter that is a traditional wired 1/5A current transformer operated meter. Configurable for 1p2w, 3p3w and 3p4w systems and hosting a vast range of measuring parameters such as Amps, Volts, Power, Power and Current Demand (Sliding and fix scale options), Power Factor, imported and exported kWh, Individual harmonics, Phase sequence and a phase summary page. It is one of the most user-friendly multifunction power meters in the market form installation to end client use.
It is typical in most installations that the current transformers are mounted on the left-hand side of the breaker so P1 is facing the correct way. However, it is also possible to mount the current transformer on the right-hand side with P2 facing the breaker. This is possible due to the meter having the option to reverse the flow to correct this type of application.
The SMART X96-5 requires mains voltage inputs and external current transformers in order to operate, it is self-supplied via a internal three phase transformer, this means if any of the phases fail the meter will remain powered and does not require an external auxiliary supply. The Smart X96-5 meter comes complete with RS485 Modbus RTU and dual pulsed outputs as standard.
input register | Measurement | Variable | Unit | Note |
---|---|---|---|---|
30001 | Phase 1 line to neutral volts | Float | V | |
30003 | Phase 2 line to neutral volts | Float | V | |
30005 | Phase 3 line to neutral volts | Float | V | |
30007 | Phase 1 current | Float | A | |
30009 | Phase 2 current | Float | A | |
30011 | Phase 3 current | Float | A | |
30013 | Phase 1 active power | Float | W | |
30015 | Phase 2 active power | Float | W | |
30017 | Phase 3 active power | Float | W | |
30019 | Phase 1 apparent power | Float | VA | |
30021 | Phase 2 apparent power | Float | VA | |
30023 | Phase 3 apparent power | Float | VA | |
30025 | Phase 1 reactive power | Float | VAr | |
30027 | Phase 2 reactive power | Float | VAr | |
30029 | Phase 3 reactive power | Float | VAr | |
30031 | Phase 1 power factor | Float | None | Positive: forward current, negative: reverse current |
30033 | Phase 2 power factor | Float | None | Positive: forward current, negative: reverse current |
30035 | Phase 3 power factor | Float | None | Positive: forward current, negative: reverse current |
30037 | Phase 1 phase angle | Float | ° | |
30039 | Phase 2 phase angle | Float | ° | |
30041 | Phase 3 phase angle | Float | ° | |
30043 | Average line to neutral volts | Float | V | |
30047 | Average line current | Float | A | |
30049 | Sum of line currents | Float | A | |
30053 | Total system power | Float | W | |
30057 | Total system volt amps | Float | VA | |
30061 | Total system V Ar | Float | VAr | |
30063 | Total system power factor (1) | Float | None | Positive: forward current, negative: reverse current |
30067 | Total system phase angle | Float | Degrees | |
30071 | Frequency of supply voltages | Float | Hz | |
30073 | Import Wh since last reset | Float | kWh | |
30075 | Export Wh since last reset | Float | kWh | |
30077 | Import V Arh since last reset | Float | kVArh | |
30079 | Export V Arh since last reset | Float | kVArh | |
30081 | VAh since last reset | Float | kVAh | |
30083 | Ah since last reset | Float | Ah | |
30085 | Total system power demand | Float | W | The power sum demand calculation is for import - export |
30087 | Maximum total system power demand | Float | W | The power sum demand calculation is for import - export |
30089 | Import active power demand | Float | W | |
30091 | Import active power max. demand | Float | W | |
30093 | Export active power demand | Float | W | |
30095 | Export active power max. demand | Float | W | |
30101 | Total system VA demand | Float | VA | |
30103 | Maximum total system VA demand | Float | VA | |
30105 | Neutral current demand | Float | A | |
30107 | Maximum neutral current demand | Float | A | |
30109 | Total system reactive power demand | Float | VAr | The power sum demand calculation is for import - export |
30111 | Maximum total system reactive power demand | Float | VAr | |
30161 | Voltage phase sequence (normal= 1, reverse=2) | Float | None | |
30163 | Current phase sequence (normal= 1, reverse=2) | Float | None | |
30193 | Nature of the load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30195 | Nature of L1 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30197 | Nature of L2 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30199 | Nature of L3 load (Resistive= 1, inductive= 2, capacitive= 3) | Float | None | |
30201 | Line 1 to Line 2 volts | Float | V | |
30203 | Line 2 to Line 3 volts | Float | V | |
30205 | Line 3 to Line 1 volts | Float | V | |
30207 | Average line to line volts | Float | V | |
30225 | Neutral current | Float | A | |
30235 | Phase 1 LIN volts THD | Float | % | |
30237 | Phase 2 LIN volts THD | Float | % | |
30239 | Phase 3 LIN volts THD | Float | % | |
30241 | Phase 1 Current THD | Float | % | |
30243 | Phase 2 Current THD | Float | % | |
30245 | Phase 3 Current THD | Float | % | |
30249 | Average line to neutral volts THD | Float | % | |
30251 | Average line current THD | Float | % | |
30259 | Phase 1 current demand | Float | A | |
30261 | Phase 2 current demand | Float | A | |
30263 | Phase 3 current demand | Float | A | |
30265 | Maximum phase 1 current demand | Float | A | |
30267 | Maximum phase 2 current demand | Float | A | |
30269 | Maximum phase 3 current demand | Float | A | |
30335 | Line 1 to line 2 volts THD | Float | % | |
30337 | Line 2 to line 3 volts THD | Float | % | |
30339 | Line 3 to line 1 volts THD | Float | % | |
30341 | Average line to line volts THD | Float | % | |
30343 | Total kwh | Float | kWh | Total kWh/ kVarh equals to Import+ export |
30345 | Total kvarh | Float | kVArh | Total kWh/ kVarh equals to Import+ export |
30347 | LI import kwh | Float | kWh | |
30349 | L2 import kwh | Float | kWh | |
30351 | L3 import kWh | Float | kWh | |
30353 | LI export kWh | Float | kWh | |
30355 | L2 export kwh | Float | kWh | |
30357 | L3 export kWh | Float | kWh | |
30359 | LI total kwh | Float | kWh | |
30361 | L2 total kWh | Float | kWh | |
30363 | L3 total kwh | Float | kWh | |
30365 | LI import kvarh | Float | kVArh | |
30367 | L2 import kvarh | Float | kVArh | |
30369 | L3 import kvarh | Float | kVArh | |
30371 | LI export kvarh | Float | kVArh | |
30373 | L2 export kvarh | Float | kVArh | |
30375 | L3 export kvarh | Float | kVArh | |
30377 | LI total kvarh | Float | kVArh | |
30379 | L2 total kvarh | Float | kVArh | |
30381 | L3 total kvarh | Float | kVArh | |
30403 | Voltage 2st- 63st Harmonic L1 | 62*Float | % | |
30527 | Voltage 2st- 63st Harmonic L2 | 62*Float | % | |
30651 | Voltage 2st- 63st Harmonic L3 | 62*Float | % | |
30775 | Current 2st- 63st Harmonic L1 | 62*Float | % | |
30899 | Current 2st- 63st Harmonic L2 | 62*Float | % | |
31023 | Current 2st- 63st Harmonic L3 | 62*Float | % | |
31147 | Voltage Total Harmonic L1 | Float | % | |
31149 | Voltage Total Harmonic L2 | Float | % | |
31151 | Voltage Total Harmonic L3 | Float | % | |
31153 | Current Total Harmonic L1 | Float | % | |
31155 | Current Total Harmonic L2 | Float | % | |
31157 | Current Total Harmonic L3 | Float | % |