Line 54: | Line 54: | ||
|**2nd Modbus read block**||||| | |**2nd Modbus read block**||||| | ||
|30080|VAh since last reset|Float|kVAh|Basis 0x50 (80), 31 words| | |30080|VAh since last reset|Float|kVAh|Basis 0x50 (80), 31 words| | ||
- | |30082|Ah since last reset|Float|Ah|0x52| | + | |30082|Ah since last reset|Float|Ah|0x02| |
- | |30084|Total system power demand|Float|W|0x54 \\ The power sum demand calculation is for import - export| | + | |30084|Total system power demand|Float|W|0x04 \\ The power sum demand calculation is for import - export| |
- | |30086|Maximum total system power demand|Float|W|0x56 \\ The power sum demand calculation is for import - export| | + | |30086|Maximum total system power demand|Float|W|0x06 \\ The power sum demand calculation is for import - export| |
- | |30088|Import active power demand|Float|W|0x58| | + | |30088|Import active power demand|Float|W|0x08| |
- | |30090|Import active power max. demand|Float|W|0x5A| | + | |30090|Import active power max. demand|Float|W|0x0A| |
- | |30092|Export active power demand|Float|W|0x5C| | + | |30092|Export active power demand|Float|W|0x0C| |
- | |30094|Export active power max. demand|Float|W|0x5E| | + | |30094|Export active power max. demand|Float|W|0x0E| |
- | |30100|Total system VA demand|Float|VA|0x64| | + | |30100|Total system VA demand|Float|VA|0x14| |
- | |30102|Maximum total system VA demand|Float|VA|| | + | |30102|Maximum total system VA demand|Float|VA|0x16| |
- | |30104|Neutral current demand|Float|A|| | + | |30104|Neutral current demand|Float|A|0x18| |
- | |30106|Maximum neutral current demand|Float|A|| | + | |30106|Maximum neutral current demand|Float|A|0x1A| |
- | |30108|Total system reactive power demand|Float|VAr|The power sum demand calculation is for import - export| | + | |30108|Total system reactive power demand|Float|VAr|0x1C \\ The power sum demand calculation is for import - export| |
- | |30110|Maximum total system reactive power demand|Float|VAr|| | + | |30110|Maximum total system reactive power demand|Float|VAr|0x1E| |
|30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None|| | |30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None|| | ||
|30162|Current phase sequence (normal= 1, reverse=2)|Float|None|| | |30162|Current phase sequence (normal= 1, reverse=2)|Float|None|| |