Line 54: Line 54:
 |**2nd Modbus read block**||||| |**2nd Modbus read block**|||||
 |30080|VAh since last reset|Float|kVAh|Basis 0x50 (80), 31 words| |30080|VAh since last reset|Float|kVAh|Basis 0x50 (80), 31 words|
-|30082|Ah since last reset|Float|Ah|0x52+|30082|Ah since last reset|Float|Ah|0x02
-|30084|Total system power demand|Float|W|0x54 \\ The power sum demand calculation is for import - export| +|30084|Total system power demand|Float|W|0x04 \\ The power sum demand calculation is for import - export| 
-|30086|Maximum total system power demand|Float|W|0x56 \\ The power sum demand calculation is for import - export| +|30086|Maximum total system power demand|Float|W|0x06 \\ The power sum demand calculation is for import - export| 
-|30088|Import active power demand|Float|W|0x58+|30088|Import active power demand|Float|W|0x08
-|30090|Import active power max. demand|Float|W|0x5A+|30090|Import active power max. demand|Float|W|0x0A
-|30092|Export active power demand|Float|W|0x5C+|30092|Export active power demand|Float|W|0x0C
-|30094|Export active power max. demand|Float|W|0x5E+|30094|Export active power max. demand|Float|W|0x0E
-|30100|Total system VA demand|Float|VA|0x64+|30100|Total system VA demand|Float|VA|0x14
-|30102|Maximum total system VA demand|Float|VA|| +|30102|Maximum total system VA demand|Float|VA|0x16
-|30104|Neutral current demand|Float|A|| +|30104|Neutral current demand|Float|A|0x18
-|30106|Maximum neutral current demand|Float|A|| +|30106|Maximum neutral current demand|Float|A|0x1A
-|30108|Total system reactive power demand|Float|VAr|The power sum demand calculation is for import - export| +|30108|Total system reactive power demand|Float|VAr|0x1C \\ The power sum demand calculation is for import - export| 
-|30110|Maximum total system reactive power demand|Float|VAr||+|30110|Maximum total system reactive power demand|Float|VAr|0x1E|
 |30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None|| |30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None||
 |30162|Current phase sequence (normal= 1, reverse=2)|Float|None|| |30162|Current phase sequence (normal= 1, reverse=2)|Float|None||