meta data for this page
Differences
This shows you the differences between two versions of the page.
Both sides previous revisionPrevious revisionNext revision | Previous revision | ||
com:eastron_smart_x96 [2025/03/05 21:22] – vamsan | com:eastron_smart_x96 [2025/03/05 21:39] (current) – vamsan | ||
---|---|---|---|
Line 17: | Line 17: | ||
===== Modbus map ===== | ===== Modbus map ===== | ||
^input register^Measurement^Variable^Unit^Note| | ^input register^Measurement^Variable^Unit^Note| | ||
- | |30000|Phase 1 line to neutral volts|Float|V|Basis 0, 0x00| | + | |**1st Modbus read block**||||| |
+ | |30000|Phase 1 line to neutral volts|Float|V|**1: | ||
|30002|Phase 2 line to neutral volts|Float|V|0x02| | |30002|Phase 2 line to neutral volts|Float|V|0x02| | ||
|30004|Phase 3 line to neutral volts|Float|V|0x04| | |30004|Phase 3 line to neutral volts|Float|V|0x04| | ||
Line 41: | Line 42: | ||
|30046|Average line current|Float|A|0x2E| | |30046|Average line current|Float|A|0x2E| | ||
|30048|Sum of line currents|Float|A|0x30| | |30048|Sum of line currents|Float|A|0x30| | ||
- | |30052|Total system power|Float|W|| | + | |30052|Total system power|Float|W|0x34| |
- | |30056|Total system volt amps|Float|VA|| | + | |30056|Total system volt amps|Float|VA|0x38| |
- | |30060|Total system V Ar|Float|VAr|| | + | |30060|Total system V Ar|Float|VAr|0x3C| |
- | |30062|Total system power factor | + | |30062|Total system power factor|Float|None|0x3E \\ Positive: forward current, |
- | |30066|Total system phase angle|Float|Degrees|| | + | |30066|Total system phase angle|Float|Degrees|0x42| |
- | |30070|Frequency of supply voltages|Float|Hz|| | + | |30070|Frequency of supply voltages|Float|Hz|0x46| |
- | |30072|Import Wh since last reset|Float|kWh|| | + | |30072|Import Wh since last reset|Float|kWh|0x48| |
- | |30074|Export Wh since last reset|Float|kWh|| | + | |30074|Export Wh since last reset|Float|kWh|0x4A| |
- | |30076|Import V Arh since last reset|Float|kVArh|| | + | |30076|Import V Arh since last reset|Float|kVArh|0x4C| |
- | |30078|Export V Arh since last reset|Float|kVArh|| | + | |30078|Export V Arh since last reset|Float|kVArh|0x4E| |
- | |30080|VAh since last reset|Float|kVAh|| | + | |**2nd Modbus read block**||||| |
- | |30082|Ah since last reset|Float|Ah|| | + | |30080|VAh since last reset|Float|kVAh|Basis 0x50 (80), 31 words| |
- | |30084|Total system power demand|Float|W|The power sum demand calculation is for import - export| | + | |30082|Ah since last reset|Float|Ah|0x02| |
- | |30086|Maximum total system power demand|Float|W|The power sum demand calculation is for import - export| | + | |30084|Total system power demand|Float|W|0x04 \\ The power sum demand calculation is for import - export| |
- | |30088|Import active power demand|Float|W|| | + | |30086|Maximum total system power demand|Float|W|0x06 \\ The power sum demand calculation is for import - export| |
- | |30090|Import active power max. demand|Float|W|| | + | |30088|Import active power demand|Float|W|0x08| |
- | |30092|Export active power demand|Float|W|| | + | |30090|Import active power max. demand|Float|W|0x0A| |
- | |30094|Export active power max. demand|Float|W|| | + | |30092|Export active power demand|Float|W|0x0C| |
- | |30100|Total system VA demand|Float|VA|| | + | |30094|Export active power max. demand|Float|W|0x0E| |
- | |30102|Maximum total system VA demand|Float|VA|| | + | |30100|Total system VA demand|Float|VA|0x14| |
- | |30104|Neutral current demand|Float|A|| | + | |30102|Maximum total system VA demand|Float|VA|0x16| |
- | |30106|Maximum neutral current demand|Float|A|| | + | |30104|Neutral current demand|Float|A|0x18| |
- | |30108|Total system reactive power demand|Float|VAr|The power sum demand calculation is for import - export| | + | |30106|Maximum neutral current demand|Float|A|0x1A| |
- | |30110|Maximum total system reactive power demand|Float|VAr|| | + | |30108|Total system reactive power demand|Float|VAr|0x1C \\ The power sum demand calculation is for import - export| |
+ | |30110|Maximum total system reactive power demand|Float|VAr|0x1E| | ||
|30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None|| | |30160|Voltage phase sequence (normal= 1, reverse=2)|Float|None|| | ||
|30162|Current phase sequence (normal= 1, reverse=2)|Float|None|| | |30162|Current phase sequence (normal= 1, reverse=2)|Float|None|| | ||
Line 96: | Line 98: | ||
|30342|Total kwh|Float|kWh|Total kWh/ kVarh equals to Import+ export| | |30342|Total kwh|Float|kWh|Total kWh/ kVarh equals to Import+ export| | ||
|30344|Total kvarh|Float|kVArh|Total kWh/ kVarh equals to Import+ export| | |30344|Total kvarh|Float|kVArh|Total kWh/ kVarh equals to Import+ export| | ||
- | |30346|LI import kwh|Float|kWh|| | + | |30346|L1 import kwh|Float|kWh|| |
|30348|L2 import kwh|Float|kWh|| | |30348|L2 import kwh|Float|kWh|| | ||
|30350|L3 import kWh|Float|kWh|| | |30350|L3 import kWh|Float|kWh|| | ||
- | |30352|LI export kWh|Float|kWh|| | + | |30352|L1 export kWh|Float|kWh|| |
|30354|L2 export kwh|Float|kWh|| | |30354|L2 export kwh|Float|kWh|| | ||
|30356|L3 export kWh|Float|kWh|| | |30356|L3 export kWh|Float|kWh|| | ||
- | |30358|LI total kwh|Float|kWh|| | + | |30358|L1 total kwh|Float|kWh|| |
|30360|L2 total kWh|Float|kWh|| | |30360|L2 total kWh|Float|kWh|| | ||
|30362|L3 total kwh|Float|kWh|| | |30362|L3 total kwh|Float|kWh|| | ||
- | |30364|LI import kvarh|Float|kVArh|| | + | |30364|L1 import kvarh|Float|kVArh|| |
|30366|L2 import kvarh|Float|kVArh|| | |30366|L2 import kvarh|Float|kVArh|| | ||
|30368|L3 import kvarh|Float|kVArh|| | |30368|L3 import kvarh|Float|kVArh|| | ||
- | |30370|LI export kvarh|Float|kVArh|| | + | |30370|L1 export kvarh|Float|kVArh|| |
|30372|L2 export kvarh|Float|kVArh|| | |30372|L2 export kvarh|Float|kVArh|| | ||
|30374|L3 export kvarh|Float|kVArh|| | |30374|L3 export kvarh|Float|kVArh|| | ||
- | |30376|LI total kvarh|Float|kVArh|| | + | |30376|L1 total kvarh|Float|kVArh|| |
|30378|L2 total kvarh|Float|kVArh|| | |30378|L2 total kvarh|Float|kVArh|| | ||
|30380|L3 total kvarh|Float|kVArh|| | |30380|L3 total kvarh|Float|kVArh|| |