lamaPLC: PTA8C04 4-channel PT100 Modbus Modul

PTA8C04 Modbus settings

Default settings: SlaveID: 1, 9600 baud, parity: N,8,1

holding register addressesNumber of registersDescriptionUnitNote
0 .. 34CH0 .. CH03 Temperature values0.1 °Cread-only, 182 → 18.2 °C
32 .. 354CH0 .. CH03 Resistance values0.1 Ohmread-only
64 .. 674CH0 .. CH03 Temperature correction values0.1 °Cr/w; read 0xFFFF
96 .. 994CH0 .. CH03 Resistance correction values0.1 Ohmr/w; read 0xFFFF
2501Automatic upload of temperatureSecond0: by query (default), 1..255 sec raster
2511Factory data reset-Feedback by reset: FF 06 00 FB 00 00 ED E5
2521Data return delayms0..1000
2531RS 485 Modbus RTU AddressRead: 0xFFFF, write 0..254
2541Baudrate0..8; 0: 1200, 1: 2400, 2: 4800, 3: 9600 (default), 4: 19200, 5: 38400, 6: 57600, 7: 115200, 8: Factory reset
2551Parity0: none (default), 1: even, 2: odd