| * Block 0: **1** – In this case, the first unit of the power plant | * Block 0: **1** – In this case, the first unit of the power plant | ||
| * Block 1: **2LAC03**: | * Block 1: **2LAC03**: | ||
| - | * Main group 2L: 2. Steam, water, gas cycle group | + | * Main group **2L**: 2. Steam, water, gas cycle group |
| - | * Subgroup 2LA: Feedwater system | + | * Subgroup |
| - | * Subgroup 2LAC: 2. feedwater pump system | + | * Subgroup |
| * 2LAC03: third feedwater pump system | * 2LAC03: third feedwater pump system | ||
| * Block 2: **CT002** | * Block 2: **CT002** | ||
| - | * Main group C: Direct measurement | + | * Main group **C**: Direct measurement |
| - | * Subgroup CT: temperature measurement | + | * Subgroup |
| - | * CT002: second temperature measurement | + | |
| * Block 3: **QT12** | * Block 3: **QT12** | ||
| - | * Main group K: I&C equipment | + | * Main group **Q**: I&C equipment |
| - | * Subgroup QT: Sensor protection of protective pipes | + | * Subgroup |
| - | * QT12: Sensor protection of 12. protective pipe | + | |
| - | That is, the above KKS code hides the 12th protective pipe protection of the 3rd pump of the second feedwater system of the first power plant unit. | + | That is, the above KKS code hides the protection of the 12th protective pipe for the third pump of the second feedwater system of the first power plant unit. |