meta data for this page
  •  

This is an old revision of the document!


Differences between the Siemens SENTRON PAC2xxx, PAC3xxx, and PAC4xxx

The differences in structure among the Siemens SENTRON PAC2xxx, PAC3xxx, and PAC4xxx power monitoring series are summarized below, focusing on their physical placement, measurement accuracy, communication capabilities, and compliance status.

Some Sentron types compare

Unit ModelBase & Optional Communication ProtocolsNetwork Configuration (Phase/Wire)MID Certification StatusAccuracy Limits (Active Energy)Harmonic Limits & Features
PAC2200Modbus TCP or Modbus RTU (Fixed variant via hardware selection)1-phase, 2-phase, or 3-phase (up to 3-wire/4-wire)Yes (Dedicated MID variants available)Class 1 (IEC 62053-21) / Class B (MID)Total Harmonic Distortion (THD) only
PAC3100Modbus RTU (Integrated); No optional slots1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 1 (IEC 62053-21)No structural harmonics tracking
PAC3120Modbus RTU (Integrated)1-phase, 2-phase, or 3-phase (3-wire/4-wire)Yes (Dedicated MID variants available)Class 1 (IEC 61557-12)THD for Voltage and Current
PAC3200Modbus TCP (Integrated). Optional: PROFINET, PROFIBUS, Modbus RTU1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.5S (IEC 62053-22)Odd harmonics up to the 31st
PAC3200TModbus TCP (Integrated). Optional via Proxy: PROFINET1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.5% (IEC 61557-12)THD and asymmetry limits
PAC32202x Modbus TCP (Dual RJ45 port). Optional: PROFINET, PROFIBUS1-phase, 2-phase, or 3-phase (3-wire/4-wire)Yes (Dedicated MID variants available)Class 0.5S (IEC 62053-22)Odd harmonics up to the 31st
PAC4200Modbus TCP (Integrated). Optional: PROFINET, PROFIBUS, Modbus RTU Gateway1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.2 (IEC 61557-12)Comprehensive tracking up to the 64th
PAC42202x Modbus TCP (Dual port, 12 links). Optional: PROFINET, PROFIBUS1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.2 (IEC 61557-12)Comprehensive tracking up to the 64th
Sentron 9410Dual-port Modbus TCP, Modbus RTU, ION Protocol, IEC 61850, DNP31-phase, 2-phase, or 3-phase (3-wire/4-wire)No (Meets ANSI C12.20 Revenue class)Class 0.2S (Ultra-high precision)Individual harmonics up to the 63rd + Waveform capture
Sentron 9810Dual-port Modbus TCP, Modbus RTU, ION Protocol, IEC 61850, DNP3, DLMS1-phase, 2-phase, or 3-phase (3-wire/4-wire)No (Meets ANSI C12.20 Revenue class)Class 0.1 (Laboratory grade standard)Advanced grid analysis up to the 127th + Transient recording