meta data for this page
  •  

This is an old revision of the document!


Sentron types

Unit ModelBase & Optional Communication ProtocolsNetwork Configuration (Phase/Wire)MID Certification StatusAccuracy Limits (Active Energy)Harmonic Limits & Features
PAC2200Modbus TCP or Modbus RTU (Fixed variant via hardware selection)1-phase, 2-phase, or 3-phase (up to 3-wire/4-wire)Yes (Dedicated MID variants available)Class 1 (IEC 62053-21) / Class B (MID)Total Harmonic Distortion (THD) only
PAC3100Modbus RTU (Integrated); No optional slots1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 1 (IEC 62053-21)No structural harmonics tracking
PAC3120Modbus RTU (Integrated)1-phase, 2-phase, or 3-phase (3-wire/4-wire)Yes (Dedicated MID variants available)Class 1 (IEC 61557-12)THD for Voltage and Current
PAC3200Modbus TCP (Integrated). Optional: PROFINET, PROFIBUS, Modbus RTU1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.5S (IEC 62053-22)Odd harmonics up to the 31st
PAC3200TModbus TCP (Integrated). Optional via Proxy: PROFINET1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.5% (IEC 61557-12)THD and asymmetry limits
PAC32202x Modbus TCP (Dual RJ45 port). Optional: PROFINET, PROFIBUS1-phase, 2-phase, or 3-phase (3-wire/4-wire)Yes (Dedicated MID variants available)Class 0.5S (IEC 62053-22)Odd harmonics up to the 31st
PAC4200Modbus TCP (Integrated). Optional: PROFINET, PROFIBUS, Modbus RTU Gateway1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.2 (IEC 61557-12)Comprehensive tracking up to the 64th
PAC42202x Modbus TCP (Dual port, 12 links). Optional: PROFINET, PROFIBUS1-phase, 2-phase, or 3-phase (3-wire/4-wire)NoClass 0.2 (IEC 61557-12)Comprehensive tracking up to the 64th
Sentron 9410Dual-port Modbus TCP, Modbus RTU, ION Protocol, IEC 61850, DNP31-phase, 2-phase, or 3-phase (3-wire/4-wire)No (Meets ANSI C12.20 Revenue class)Class 0.2S (Ultra-high precision)Individual harmonics up to the 63rd + Waveform capture
Sentron 9810Dual-port Modbus TCP, Modbus RTU, ION Protocol, IEC 61850, DNP3, DLMS1-phase, 2-phase, or 3-phase (3-wire/4-wire)No (Meets ANSI C12.20 Revenue class)Class 0.1 (Laboratory grade standard)Advanced grid analysis up to the 127th + Transient recording