The Eastron SDM630 is a series of three-phase, multifunctional DIN-rail-mounted energy meters used to measure and monitor electrical parameters in industrial, commercial, and residential applications. It is known for its high accuracy, compact design, and communication interfaces.
Key Features
According to Eastron Europe datasheets and user manuals, the specifications for the standard SDM630 models are as follows:
| Parameter | Specification |
|---|---|
| Nominal Voltage (Un) | 3×230/400 V AC |
| Maximum Current (Imax) | 100 A (direct measurement) |
| Accuracy Class | Class 1 (IEC 62053-21) / Class B (EN50470-3) |
| Frequency Range | 50 or 60 Hz |
| Communication | RS485 Modbus RTU, two pulsed outputs |
| Display | Backlit LCD |
| Mounting | 35mm DIN rail |
| Protection Degree | IP51 (indoor use) |
| Operating Temperature | -25°C to +55°C |
The primary difference among the Eastron SDM630 V1, V2, and V3 versions lies in the firmware and specific energy calculation methods, particularly how the meters handle imported and exported energy.
Key Differences Summary
Detailed Comparison Points
| Feature | SDM630 V1 | SDM630 V2 | SDM630 V3 |
|---|---|---|---|
| Energy Calculation | Basic Import/Export | Net-counting (Total = Import - Export) | Net-counting, often with separate registers |
| Resettable Energy | Limited options | Includes second resettable total energy counter | Same as V2, possibly enhanced options |
| Firmware Date | Older builds | Typically prior to 2022 | Typically 2022 or later |
| Modbus Registers | Limited set | More extensive, with added registers | Largely consistent with V2 core registers |
| Certifications | Standard | Standard, and MID options | Standard and MID options, focus on recent compliance |
Modbus Protocol Consistency
Crucially, the core Modbus register addresses for real-time measurements (voltage, current, power, frequency) are largely identical across all versions. The main differences users encounter typically relate to the interpretation of the total energy registers and minor menu/configuration variations.
The default Modbus communication settings (Address 1, 9600 baud, 8N1) are generally consistent across all three versions, though supplier customizations exist.
Read Limits: Do not attempt to read more than 40 parameters (80 registers) in a single Modbus request to avoid exception errors.
RS485 communication interface, MODBUS RTU protocol:
The registers are read-only.
| Register Nr | 32 bit address | Description | Unit |
|---|---|---|---|
| 30001 | 1 | Phase 1 line to neutral volts | Volts |
| 30003 | 2 | Phase 2 line to neutral volts | Volts |
| 30005 | 3 | Phase 3 line to neutral volts | Volts |
| 30007 | 4 | Phase 1 current | Amps |
| 30009 | 5 | Phase 2 current | Amps |
| 30011 | 6 | Phase 3 current | Amps |
| 30013 | 7 | Phase 1 power | Watts |
| 30015 | 8 | Phase 2 power | Watts |
| 30017 | 9 | Phase 3 power | Watts |
| 30019 | 10 | Phase 1 volt amps | VA |
| 30021 | 11 | Phase 2 volt amps | VA |
| 30023 | 12 | Phase 3 volt amps | VA |
| 30025 | 13 | Phase 1 volt amps reactive | VAr |
| 30027 | 14 | Phase 2 volt amps reactive | VAr |
| 30029 | 15 | Phase 3 volt amps reactive | VAr |
| 30031 | 16 | Phase 1 power factor (1) | VAr |
| 30033 | 17 | Phase 2 power factor (1) | VAr |
| 30035 | 18 | Phase 3 power factor (1) | VAr |
| 30037 | 19 | Phase 1 phase angle | Degrees |
| 30039 | 20 | Phase 2 phase angle | Degrees |
| 30041 | 21 | Phase 3 phase angle | Degrees |
| 30043 | 22 | Average line to neutral volts | Volts |
| 30047 | 24 | Average line current | Amps |
| 30049 | 25 | Sum of line currents | Amps |
| 30053 | 27 | Total system power | Watts |
| 30057 | 29 | Total system volt amps | VA |
| 30061 | 31 | Total system VAr | VAr |
| 30063 | 32 | Total system power factor (1) | - |
| 30067 | 34 | Total system phase angle | Degrees |
| 30071 | 36 | Frequency of supply voltages | Hz |
| 30073 | 37 | Total Import kWh | kWh |
| 30075 | 38 | Total Export kWh | kWh |
| 30077 | 39 | Total Import kVArh | kVArh |
| 30079 | 40 | Total Export kVArh | kVArh |
| 30081 | 41 | Total VAh | kVAh |
| 30083 | 42 | Ah | Ah |
| 30085 | 43 | Total system power demand (2) | W |
| 30087 | 44 | Maximum total system power demand (2) | VA |
| 30101 | 51 | Total system VA demand | VA |
| 30103 | 52 | Maximum total system VA demand | VA |
| 30105 | 53 | Neutral current demand | Amps |
| 30107 | 54 | Maximum neutral current demand | Amps |
| 30201 | 101 | Line 1 to Line 2 volts | Volts |
| 30203 | 102 | Line 2 to Line 3 volts | Volts |
| 30205 | 103 | Line 3 to Line 1 volts | Volts |
| 30207 | 104 | Average line to line volts | Volts |
| 30225 | 113 | Neutral current | Amps |
| 30235 | 118 | Phase 1 L/N volts THD | % |
| 30237 | 119 | Phase 2 L/N volts THD | % |
| 30239 | 120 | Phase 3 L/N volts THD | % |
| 30241 | 121 | Phase 1 Current THD | % |
| 30243 | 122 | Phase 2 Current THD | % |
| 30245 | 123 | Phase 3 Current THD | % |
| 30249 | 125 | Average line to neutral volts THD | % |
| 30251 | 126 | Average line current THD | % |
| 30255 | 128 | Total system power factor (5) | Degrees |
| 30259 | 130 | Phase 1 current demand | Amps |
| 30261 | 131 | Phase 2 current demand | Amps |
| 30263 | 132 | Phase 3 current demand | Amps |
| 30265 | 133 | Maximum phase 1 current demand | Amps |
| 30267 | 134 | Maximum phase 2 current demand | Amps |
| 30269 | 135 | Maximum phase 3 current demand | Amps |
| 30335 | 168 | Line 1 to line 2 volts THD | % |
| 30337 | 169 | Line 2 to line 3 volts THD | % |
| 30339 | 170 | Line 3 to line 1 volts THD | % |
| 30341 | 171 | Average line to line volts THD | % |
| 30343 | 172 | Total kwh | kwh |
| 30345 | 173 | Total kvarh | kvarh |
| 30347 | 174 | L1 import kwh | kwh |
| 30349 | 175 | L2 import kwh | kwh |
| 30351 | 176 | L3 import kwh | kwh |
| 30353 | 177 | L1 export kwh | kwh |
| 30355 | 178 | L2 export kwh | kwh |
| 30357 | 179 | L3 export kwh | kwh |
| 30359 | 180 | L1 total kwh | kwh |
| 30361 | 181 | L2 total kwh | kwh |
| 30363 | 182 | L3 total kwh | kwh |
| 30365 | 183 | L1 import kvarh | kvarh |
| 30367 | 184 | L2 import kvarh | kvarh |
| 30369 | 185 | L3 import kvarh | kvarh |
| 30371 | 186 | L1 export kvarh | kvarh |
| 30373 | 187 | L2 export kvarh | kvarh |
| 30375 | 188 | L3 export kvarh | kvarh |
| 30377 | 189 | L1 total kvarh | kvarh |
| 30379 | 190 | L2 total kvarh | kvarh |
| 30381 | 191 | L3 total kvarh | kvarh |
If you'd like to support the development of the site with the price of a coffee — or a few — please do so here.
Here's a handy tip: you can quickly save this page as a PDF by clicking “export to PDF” in the menu on the right side of the screen.
The registers are read/write.
| Address register | Parameter number | Parameter | Valid range | type | mode |
|---|---|---|---|---|---|
| 40003 | 2 | Demand period | Write demand period: 0, 5,8, 10, 15, 20, 30, or 60 minutes, default 60. Setting the period to 0 will cause the demand to show the current parameter value, and demand max to show the maximum parameter value since the last demand reset. | Length: 4 byte, Data Format: Float | rw |
| 40011 | 6 | System type | Write system type: 3p4w = 3, 3p3w = 2 & 1p2w= 1 Requires password, see parameter 13 | Length : 4 byte, Data Format : Float | rw |
| 40013 | 7 | Pulse 1 width | Write pulse1 on period in milliseconds: 60, 100, or 200, default 100. | Length: 4 byte, Data Format: Float | r |
| 40015 | 8 | Password lock | Write any value to password lock-protected registers. Read password lock status: 0 = locked. 1 = unlocked. Reading will also reset the password timeout back to one minute. | Length: 4 byte, Data Format: Float | r |
| 40019 | 10 | Network Parity Stop | Write the network port parity/stop bits for MODBUS Protocol, where: 0 = One stop bit and no parity, default. 1 = One stop bit and even parity. 2 = One stop bit and odd parity.3 = Two stop bits and no parity.Requires a restart to become effective. | Length : 4 byte, Data Format : Float | rw |
| 40021 | 11 | Network Node | Write the network port node address: 1 to 247 for MODBUS Protocol, default 1. Requires a restart to become effective. | Length : 4 byte, Data Format : Float | rw |
| 40023 | 12 | Pulse1 Divisor1 | Write pulse divisor index: n = 0 to 5 0: 0.0025 kWh(kVArh)/imp 1: 0.01 kWh(kVArh)/imp 2: 0.1 kWh(kVArh)/imp 3: 1 kWh(kVArh)/imp 4: 10 kWh(kVArh)/imp 5: 100 kWh(kVArh)/imp | Length : 4 byte, Data Format : Float | rw |
| 40025 | 13 | Password | Write password for access to protected registers. Default: 0000 | Length: 4 byte, Data Format: Float | rw |
| 40029 | 15 | Network Baud Rate | Write the network port baud rate for MODBUS Protocol, where: 0: 2400 baud 1: 4800 baud 2: 9600 baud, default 3: 19200 baud 4: 38400 baud Requires a restart to become effective | Length: 4 byte, Data Format: Float | rw |
| 40087 | 44 | Pulse 1 Energy Type | Write MODBUS Protocol input parameter for pulse output 1: 1: import active energy 2: total active energy 4: export active energy, default 5: import reactive energy 6: total reactive energy 8: export reactive energy | Length : 4 byte, Data Format : Float | rw |
| 461457 | 30729 | reset | 00 00 :reset the Maximum demand | Length : 2 byte, Data Format : Hex | w |
| Nr. of block | Start address | number of registers |
|---|---|---|
| 1 | 3000 | 100 |
| 2 | 3100 | 8 |
| 3 | 3200 | 70 |
| 4 | 3300 | 82 |
| 5 | 4000 | 100 |
The Eastron SDM630 communicates via Modbus RTU over an RS-485 interface, requiring an RS-485 converter module and a dedicated library to read data on an Arduino. The SDM_Energy_Meter library simplifies this process.
Hardware Required
Wiring Schematic (MAX485 Module)
Arduino Example Code
This example uses the SDM_Energy_Meter library by reaper7 and the standard SoftwareSerial library.
#include <SoftwareSerial.h> #include <SDM.h> // Pins for the SoftwareSerial communication // RX pin: 3, TX pin: 4 SoftwareSerial sdmSerial(3, 4); // Pin 2 is used to control the DE/RE pins of the MAX485 converter #define RS485_EN 2 // Create an SDM object (SoftwareSerial instance, Enable Pin) SDM sdm(&sdmSerial, RS485_EN); void setup() { Serial.begin(115200); // Serial monitor output sdmSerial.begin(9600); // SDM630 default baud rate Serial.println("\nEastron SDM630 Reader"); } void loop() { // Read Voltage (Register 0x0000) float voltage = sdm.readVal(SDM_PHASE_1_VOLTAGE); if (!isnan(voltage)) { Serial.print("Voltage L1: "); Serial.print(voltage); Serial.println(" V"); } else { Serial.println("Failed to read Voltage"); } // Read Total System Power (Register 0x0034 or 0x0052 depending on V1/V2/V3 meter version) // Check documentation for the specific register address float power = sdm.readVal(SDM_TOTAL_SYSTEM_POWER); if (!isnan(power)) { Serial.print("Total Power: "); Serial.print(power); Serial.println(" W"); } else { Serial.println("Failed to read Power"); } // Read Total Import Energy (Register 0x0048 or 0x0072 depending on version) float energy = sdm.readVal(SDM_TOTAL_IMPORT_ENERGY); if (!isnan(energy)) { Serial.print("Import Energy: "); Serial.print(energy); Serial.println(" kWh"); } else { Serial.println("Failed to read Energy"); } delay(3000); // Wait 3 seconds before next read }