LamaPLC: Eastron SDM 230 Communication

Eastron SDM230

The Eastron SDM230-Modbus MID 1-phase kWh meter is ideal for the precise monitoring of, for example, a solar panel system, a charging station, a heat pump or another 1-phase group of your choice. On the illuminated LCD screen, you can immediately see how many kWh the respective system consumes or produces and is used for official registration and billing of the measurement data. For example, if you want to bill a tenant for the electricity consumption of a specific room.

RS485 communication interface, MODBUS RTU protocol:

32 bit (2 words) input registers

The registers are read-only.

CodeRegister NrDescriptionTypeUnit
V130001Line neutral voltFloatV
C130007CurrentFloatA
ACP130013Active powerFloatW
APP130019Apparent powerFloatVA
RAP130025Reactive powerFloatVAr
PF130031Power factorFloat-
PA130037Phase angleFloat°
FR130071FrequencyFloatHz
IACE130073Import active energyFloatkWh
EACE130075Export active energyFloatkWh
IRAE130077Import reactive energyFloatkvarh
ERAE130079Export reactive energyFloatkvarh
TP30085Total system power demandFloatW
-30087Maximum total system power demandFloatW
-30089Current system positive power demandFloatW
-30091Maximum system positive power demandFloatW
-30093Current system reverse power demandFloatW
-30095Maximum system reverse power demandFloatW
-30259Current demandFloatA
-30265Maximum current demandFloatA
TAE30343Total active energyFloatkWh
TRE30345Total reactive energyFloatkvarh
-30385Current resettable total active energyFloatkWh
-30387Current resettable total reactive energyFloatkvarh
MA40021Modbus node address
RW, default 45
Float-
MBR40029Modbus baud rate
RW, 0 = 2400 bps(default) 1 = 4800 bps 2 = 9600 bps 5=1200 bps
Float-


This page has been accessed for: Today: 1, Until now: 61