====== lamaPLC: Communication with B+G E-Tech DS100 Serie Modbus ====== The digital bidirectional power meter in this series is designed for direct measurement in 3-phase AC systems with maximum loads of up to 100 A. This meter is MID B&D certified by SGS UK. |{{:com:ds100_1.jpg?300|DS100 Serie Modbus}}|{{:com:ds100_2.jpg?300|DS100 Serie Modbus}}|{{:com:ds100_3.jpg?300|DS100 Serie Modbus}}| ===== Technical data ===== * Type designation: DS100-009 (Article no. 1042204-M23) * MID certified according to certificate 0120/SGS0622 from SGS UK * 0.25-5A nominal current / 100A limit current (limit current = can be continuously loaded!) * Electronic electricity meter (3-phase current according to EN 61036, for 4-wire three-phase networks) 3p4w * digital LCD (backlit) * 6 digital digits + 2 decimal places = 999999.99 kWh * Connection: 3x230V/400V AC * Operating range: 3*161/279 to 300/500 / 0.1 ~ 100A * Frequency range: 50Hz +/- 10% * Start current Cos-Phi = 1: 0.4% of Ib * Self-consumption: ≤ 1W /12VA per phase * Accuracy class: 1 * Pulse length: 80ms * LED counting pulses: 1000imp/kWh * Temp. range: -25°C to +55°C * Rel. humidity: up to 75% - briefly up to 95% * Mounting: DIN rail (DIN EN50022) / 4TE=71.5mm * Dimensions: 71.5x90x72mm * Weight: approx. 350g * Approved for billing purposes to third parties ===== Modbus map ===== ^Address^Measuring^Var.type^Unit/resolution^Rel.addr| |**Input register block**||||| |31024|Phase 1 to neutral volts|int32|mV|Basis 1024, 0x00, lenght: 80 word| |31026|Phase 2 to neutral volts|int32|mV|0x02| |31028|Phase 3 to neutral volts|int32|mV|0x04| |31030|Phase L1 - L2 volts|int32|mV|0x06| |31032|Phase L2 - L3 volts|int32|mV|0x08| |31034|Phase L3 - L1 volts|int32|mV|0x0A| |31036|Average line to neutral volts|int32|mV|0x0C| |31038|Average line to line volts|int32|mV|0x0E| |31040|Phase 1 current|int32|mA|0x10| |31042|Phase 2 current|int32|mA|0x12| |31044|Phase 3 current|int32|mA|0x14| |31046|Neutral current|int32|mA|0x16| |31048|Three-phase vector current|int32|mA|0x18| |31050|Phase 1 active power|int32|W|0x1A| |31052|Phase 2 active power|int32|W|0x1C| |31054|Phase 3 active power|int32|W|0x1E| |31056|Total active power|int32|W|0x20| |31058|Phase 1 apparent power|int32|VA|0x22| |31060|Phase 2 apparent power|int32|VA|0x24| |31062|Phase 3 apparent power|int32|VA|0x26| |31064|Total apparent power|int32|VA|0x28| |31066|Phase 1 reactive power|int32|var|0x2A| |31068|Phase 2 reactive power|int32|var|0x2C| |31070|Phase 3 reactive power|int32|var|0x2E| |31072|Total reactive power|int32|var|0x30| |31074|Phase 1 frequency|int16|Hz/10|0x32| |31075|Phase 2 frequency|int16|Hz/10|0x33| |31076|Phase 3 frequency|int16|Hz/10|0x34| |31077|Combinated frequency|int16|Hz/10|0x35| |31078|Phase 1 power factor|int16|0.1|0x36| |31079|Phase 2 power factor|int16|0.1|0x37| |31080|Phase 3 power factor|int16|0.1|0x38| |31081|Total power factor|int16|0.1|0x39| |31082|Phase 1 active power forward|int32|W/10|0x3A| |31084|Phase 2 active power forward|int32|W/10|0x3C| |31086|Phase 3 active power forward|int32|W/10|0x3E| |31088|Total active power forward|int32|W/10|0x40| |31090|Phase 1 active power reverse|int32|W/10|0x42| |31092|Phase 2 active power reverse|int32|W/10|0x44| |31094|Phase 3 active power reverse|int32|W/10|0x46| |31096|Total active power reverse|int32|W/10|0x48| |31098|Phase 1 active power demand|int32|W/10|0x4A| |31100|Phase 2 active power demand|int32|W/10|0x4C| |31102|Phase 3 active power demand|int32|W/10|0x4E| |31104|Total active power demand|int32|W/10|0x50| |31082|Phase 1 reactive power forward|int32|var/10|0x52| |31084|Phase 2 reactive power forward|int32|var/10|0x54| |31086|Phase 3 reactive power forward|int32|var/10|0x56| |31088|Total reactive power forward|int32|var/10|0x58| |31090|Phase 1 reactive power reverse|int32|var/10|0x60| |31092|Phase 2 reactive power reverse|int32|var/10|0x62| |31094|Phase 3 reactive power reverse|int32|var/10|0x64| |31096|Total reactive power reverse|int32|var/10|0x66| |31098|Phase 1 reactive power demand|int32|var/10|0x68| |31100|Phase 2 reactive power demand|int32|var/10|0x6A| |31102|Phase 3 reactive power demand|int32|var/10|0x6C| |31104|Total reactive power demand|int32|var/10|0x6E| |**Holding register block**||||| |40270|Total active energy forward|int32|kWh/100|Basis 270, 0x00, lenght: 52 word| |40280|Total active energy reverse|int32|kWh/100|0x0A| |40290|Total active energy|int32|kWh/100|0x14| |40300|Total reactive energy forward|int32|kvarh/100|0x1E| |40310|Total reactive energy reverse|int32|kvarh/100|0x28| |40320|Total reactive energy|int32|kvarh/100|0x32| |41280|Phase 1 active energy|int32|kWh/100|Basis 1280, 0x00, lenght: -- word| |41290|Phase 1 active energy forward|int32|kWh/100|| |41300|Phase 1 active energy reverse|int32|kWh/100|| |41310|Phase 1 reactive energy forward|int32|kvarh/100|| |41320|Phase 1 reactive energy reverse|int32|kvarh/100|| |41330|Phase 1 reactive energy|int32|kvarh/100|| |41380|Phase 2 active energy|int32|kWh/100|| |41390|Phase 2 active energy forward|int32|kWh/100|| |41400|Phase 2 active energy reverse|int32|kWh/100|| |41410|Phase 2 reactive energy forward|int32|kvarh/100|| |41420|Phase 2 reactive energy reverse|int32|kvarh/100|| |41430|Phase 2 reactive energy|int32|kvarh/100|| |41480|Phase 2 active energy|int32|kWh/100|| |41490|Phase 2 active energy forward|int32|kWh/100|| |41500|Phase 2 active energy reverse|int32|kWh/100|| |41510|Phase 2 reactive energy forward|int32|kvarh/100|| |41520|Phase 2 reactive energy reverse|int32|kvarh/100|| |41530|Phase 2 reactive energy|int32|kvarh/100||